INSTALLATION CONTINUED

STEP #4 Sensor Mounting
On-Wall Sensor
1) Center sensor eye 2-1/2" above the seat in up position, (image 17). Attach to wall using adhesive strip and/or screws & anchors (G). Note the orientation of the sensor, (image 17). WARNING: Adhesive strip can only be applied once; once installed it is difficult to remove.

2) Remove cover using key, (image 18) and install (4) AA batteries. Reattach sensor cover. To adjust sensor range see Step #5.
Center sensor eye
 
STEP #5 Adjusting AutoFlush Range

OD – Object Detection Range Adjustment – (factory setting is 32”)
ODX – Object Detection Extended Delay Range adjustment – (factory setting is 32”)

1) Remove the cover of the sensor assembly with the sensor cover key (E).
2) Remove the rubber seal located on the left side of the sensor lens.
3) Press sensor range reset button shown above (image 19).
NOTE: The green LED will flash continuously when it has an object in view during the seven minute reset period. This allows you to select the correct range.
4) Hold a white piece of paper in front of the sensor. Slowly back the paper away until the green light stops, to determine if the sensor range needs to be adjusted Near or Far (max range = 48”).
5) Use the sensor adjustment tool to turn Object Detection (OD) Adjustment Screw as needed until the light flashes with the piece of paper held at the proper range.
6) Ensure Object Lock Sensor is not detecting unwanted objects by stepping out of the sensor path making sure that the green LED is not flashing. If sensor locks onto an unwanted object, unit will not flush properly.
7) Replace sensor cover.
8) After the 7-minute reset period, the green LED will flash 3 times when a user is in view (after the 3 second delay in OD mode or 5 second delay in ODX mode).

WO – Wave Only Range Adjustment – (factory setting is 2”)

1) Remove the cover of the sensor assembly with the sensor cover key (E).
2) Remove the rubber seal located on the left side of the sensor lens.
3) Press sensor range reset button shown above (image 19).
4) Place your hand at the required wave activation distance (max range = 6”)
5) Hold a white piece of paper in front of the sensor. Slowly back the paper away until the green light stops. Determine if the sensor range needs to be adjusted Near or Far.
6) Ensure Wave Only Sensor is not detecting unwanted objects by moving your hand out of the sensor path and making sure the green LED does not turn on. If sensor locks onto an unwanted object, unit will not flush properly. Shorten, activation distance.
7) Replace sensor cover.
8) After the 7-minute reset period, the green LED will turn on when your hand is in view.

STEP #6 Test Sensor Range/Adjustment
Sensor is factory set. Green light on sensor will flash 3 times at the start of every use. Should the sensor need adjusting:
1) Remove the cover using Cover Key (E), (image 18). For On-Wall sensor, remove rubber cover concealing the reset button and range adjuster screw.
2) Depress the sensor range reset button, (image 19). During the 7 minute start up sequence the green light flashes constantly when a user is in view.
3) Using the Sensor Tool (F), turn the sensor range adjustment screw, (image 19) counter-clock wise, shortening the sensor range, until the green light stops flashing while you are standing at the front rim of the bowl. Slowly turn the sensor range adjustment screw clock-wise until the green light flashes while standing at the front of the bowl.
4) Reinstall rubber cover for On-Wall sensor and re-attach the cover.

<<BACK